Sound insulation testing is used to measure the resistance of sound provided by an element of a building (such as a floor or wall) between dwellings. It essentially measures the effectiveness of the sound proofing treatment installed as part of a build or property development. New structures and reconstructed developments have been mandated by the Building Regulations to test for sound upon completion, since Approved Document E (ADE) was reappraised in 2003.

At the completion of the test, a sound insulation certificate is issued. Without the certificate, Building Control will not release the building completion certificate to the contractors and developers of the project. As a result of this, we try to ensure that you are issued with a sound insulation certificate as fast as possible. In fact, we pride ourselves on issuing our sound insulation testing certificates as quickly as possible.

Our highly qualified site engineers can arrive on site when needed. They will provide verbal results after the test and a written report will be sent to you within 24 working hours.

Our Guarantee

  • Over 15 years experience
  • State of the art equiptment
  • Onsite Support
  • Next Day Report Turn Around
Call us today for a quote on 020 3372 4430
Or you can email us at info@af-acoustics.com

What is a Sound Insulation Test?

Walls and floors that separate dwellings in a building are expected to be sound tested, as mandated by Document E of Building Regulations. Only dwellings that have used Robust Details, which licensed before the installation, are exempted from the test. Sound testing measures the impact and airborne sound moving through new and old adjoining buildings. This tests include the boundary walls between buildings and in-between the spaces in a development.

What is involved in a Sound Test

Workers on a site will vacate the premises while the sound test is being conducted. This will facilitate an enabling and quiet environment for the tests to be carried out. The process of a sound test is determined by the size and complexity of the site being tested. Generally, a sound insulation test takes about 90 minutes for a simple, regular sized project.

After the sound insulation test, the sound testing engineer will provide provisional results whilst on-site, as well as providing basic feedback about what has been noted during the test, e.g. potential problems or any future areas of concern.

You will get a detailed written report and sound test certificate about a day after, if possible. The way a sound test is conducted is determined by ADE of Building Regulations. It mandates that in all developments, every 10 units in a group or sub-group will undertake one set of tests. It explicitly states what a sub-group is in Section 1. Buildings are divided into three kinds for the test – houses, flats and rooms built for or converted to residential dwellings, like student accommodation, care homes and hotel rooms. How much testing that is required for each category can be found below.

Why Sound Testing is Required

Sound insulation testing is required because ADE of Building Regulations has made it compulsory for all new buildings to take a sound test prior to finishing construction. Results for impact sound should be 62dB L’nTw or less while those for airborne sound insulation should be 45dB DnTw+Ctr or more. This is to be certain that all new developments meet a uniform minimum criterion for resistance to sound from other parts of the development and adjoining developments. Sound affects our life no matter where we are, at home, work or while relaxing. Places with lowered noise are more comfortable and enabling. Sound testing ensures that noise reduction in a building is effective.

Sound insulation and speech privacy are critical for a variety of reasons. Inadequate sound insulation can be extremely distressing to those affected by it. Let’s take a look at this scenario. An individual living in a block of flats might spend the weekend with friends relaxing and playing loud music. If the sound insulation on adjoining walls and floor is insufficient, the music will be distressful to neighbours, especially if they work at night. This is just one instance of the influence of sound insulation on our lives. Sound insulation is also effective in buildings that have flats with mixed uses. If the building passed the sound test, you can be sure that noise reduction will be effective.

How Do I Know if I Need a Sound Test?

You need a sound insulation test if you’re:

  • Constructing a nursing home or residential rooms like hostel or hotel rooms,
  • Converting a building with a single dwelling into flats,
  • Constructing a property with two or more units,
  • Using designs without Robust Details to build

It is imperative that sound insulation tests be undertaken, as explained and stipulated by ADE.

All you have to do is follow the guidelines listed in the document or pay to use Robust Details and you will have fulfilled the requirements. If you choose the latter, you must use Robust Details which are a approved design details for partitioning walls and floors. You also cannot expand or tweak the design from the Robust Detail Approved listing. However, you are exempt from the sound test. This becomes difficult when you need to pick a more appropriate or cost-effective design that will suit your needs. Sound tests enable you do that, making it more flexible. Conducting on-site pre-completion sound testing also enables the architects more scope with their design and can lead to improved sound insulation performance.

How much does sound insulation testing cost?

Call us or email us to get a free quotation for your building. We have handled all kinds of sound insulation projects in UK and issue a report and certificate as quickly as possible. Our prices are affordable too and can beat others.

Ideal Period for a Sound Insulation Test

The ideal period for a sound insulation test is after the fitting of windows and doors, and before the building is finished. If you want, AF Acoustics can conduct tests before then to find out if there are any problems on your property. To achieve the best results we would need the following during the test: quietness during the time of the test, 240V power supply and access to all the rooms unless a test plan has been agreed upon prior to the test time.

How a Sound Test is Done

Sound insulation testing is not complicated. Our highly qualified engineers will be willing to explain it in detail on the site. We carry out airborne and impact tests on separating floors, and airborne tests on separating walls.

The source sound is produced with a white or pink noise generator with a dodecahedron speaker in the largest room. The noise from the source room and received by the receiver room, and background noise is measured with a sound level meter. The background noise level is also measured. The higher the background noise then the higher the source noise will need to be set, since the resulting noise level in the receiver room needs to be 10dB higher than the background noise at all measured frequencies. Airborne sound tests are conducted in this manner: two singular speaker positions are used for every source room. The noise in the receiver room is measured to determine the variations in noise level between the source and receiver room.

The sound difference is adjusted to make an allowance for reverberation time (time in which the sound decays by 60dB) and background noise in the receiver room. Impact tests are conducted by fixing a tapping machine on the floor. Noise level in the room below is measured at various different frequencies. Calculations based on these measurements are undertaken and the results compared to the Building Regulations Part E requirements for the given type of the building. Without the mathematical formulae, this explanation highlights sound insulation testing procedures in a simple manner.

Call us today for a quote on 020 3372 4430
Or you can email us at info@af-acoustics.com

What Sound Insulation Testing Equipment do we use?

The testing equipment used are UKAS calibrated. Our highly qualified engineers test based on present Building Regulations conditions. An airborne sound test measures levels of sound transmitted through the air through a separating element. A loudspeaker and noise generator is used in one room while a sound level meter is used in both rooms for measuring level of noise. We use a tapping machine, which drops metal hammers onto the floor to create impact noise. We then measure the amount of sound that passes through the partition with a sound level meter in the room under the tapping machine. The tests are carried out in rooms suitable for residential use like bedrooms, lounges and kitchens. Test findings are compiled in a report and issued to the client. The report will be accepted by Building Control and used for signing off your project.

These kinds of properties should undergo a sound insulation test:

For sound testing we usually undertake impact and airborne sound test on buildings. This affects the separating floors and walls between habitable rooms of buildings and developments.

A new building with 2 or more dwellings

This is to ensure that the sound proofing of the building is up to standard for residential purposes.

A single dwelling that was turned into a development with several flats or units

When the development is completed, ADE of Building Regulations should be checked, and sound insulation tested accordingly.

Designed in a way that does not adhere to Robust Details

Robust Detail Ltd set up the Robust Detail Scheme in 2004 to make sure architect and building designs construct partition walls and floors that comply with Approved Document E sound insulation standards. If the building design is not in line with any Robust Details, it will require sound testing to ensure its compliance with the buildings regulations. The minimum criterion is based on various factors such as the purpose of the development and if it is a permanent dwelling or rooms to be used as residences like students’ accommodations and hotels.

Areas in the UK AF Acoustics Conduct Test

AF Acoustics is an acoustic consultancy providing acoustic design services to clients nationwide, especially in Charlbury. We work with architects, planning and environmental consultancies as well as private individuals and government agencies. Our consultants can be found in various places in the south east region. This way you get an affordable price.

Why AF Acoustics is the right choice for your sound insulation test

Our sound insulation testing expertise at AF Acoustics have aided several home and business owners in Charlbury. We come highly recommended by our clients because of the guarantees when you work with us

15 years’ experience

With more than 15 years of experience, we have a deep knowledge of our customers’ industry and provide actionable strong advice tailored to their needs. We also have a track record of providing superior acoustic services to our customers (home and business owners) in the UK in small and large projects, giving them astounding value for their money.

Great prices

We want to ensure that you get the best value for your money. That is why we have one of the most unbeatable rates in and outside Charlbury. Call us or email today to get a free quotation.

Ultrafast and efficient consultancy

We will listen to your wishes, provide you sturdy solutions and deliver acoustic consultancy through our expertise. When you contact us for expert direction, we make it our utmost priority and convey exact answers quickly. We suggest compelling solutions that are in accordance with your present and long-term needs.

Test dates that are adaptable

We make your convenience our priority. Therefore, we offer flexible alternatives that can help you select test dates that suit you itinerary. Take the first step towards your sound insulation testing in Charlbury by calling us now.

Test reports arrive the next day

The sooner you get a report on the completed sound insulation test, the sooner you can take appropriate action. We strive to deliver next day reporting in all scenarios regardless of the complexity or size of the project. That way, you can take immediate action on the recommendations given. Our reports are thorough and cover all the important issues.

AF Acoustics sound testing services

With AF Acoustics, you get a highly effective and expert acoustic advice which our customers all over UK have benefited from. Telephone or email us today for more data on how we can assist you with your acoustic requirements.

Airborne and impact tests for floors/ceilings

The ceilings/floors of developments undergo impact and airborne floor testing. An impact test measures the levels of noise transmitted directly through a separating construction. The adjoining floors/ceilings of rooms intended as residences usually have both impact and airborne sound tests.

ADE testing

Document E of Building Regulations requires certain criteria for the sound performance of a dwelling. Our sound insulation tests are conducted in accordance to these criteria. For new buildings, results for impact sound should be 62dB L’nTw or less while those for airborne sound insulation should be 45dB DnTw+Ctr or more. Converted structures expected impact sound results increases by 2dB L’nTw while the airborne sound results reduces by 2dB DnTw+Ctr.

Testing for sound insulation

With our professional and highly skilled expertise, we are willing to work with our clients to help them get a pass certificate in every situation. To make sure a new residence meets with the standards of greater than 45dB DnTw+Ctr and less than 62dB L’nTw, an airborne wall test and an airborne and impact floor test will need to be conducted. We regularly offer consultations to builders and project managers at the beginning of the development, so that they can take the appropriate action and are confident when it’s time to take the sound insulation test. Contact us today for more information about our sound testing services or to book a no obligation quote, free of charge.

Call us today for a quote on 020 3372 4430
Or you can email us at info@af-acoustics.com

BB93 acoustic design tests in schools

For a school to meet up with Building Regulation acoustic requirements, it must adhere to Building Bulletin 93 (BB93) which explains the sound insulation expectation for schools in detail. If you’re constructing a new school in Charlbury, we can test the sound performance to evaluate if it meets the standards of BB93.

Acoustic plan details

AF Acoustics give definite design services and consultancy services to all types of developments. We create bespoke solution and can provide information on the best available acoustic products. We will tailor our design solutions to your project.

As anybody who has needed to handle the acoustics for a building will know, it’s essential to get proper advice, early in the project from a good acoustic expert. AF Acoustics can help you with identifying the right acoustic needs and standard for your construction at the beginning period and advise you on how to meet them.

We can assist with:

Acoustic detail layout for architect developing structures complying to Building regulations, BS8233 and so on. Detail layout for the commercial, health and educational constructions in order to align with regulations. Construction designs and specifications for sound control in residential areas and other noise sensitive developments. Public address and sound reinforcement system

Call Our Experts Now For A Sound Insulation Testing Quote

Our services at AF Acoustics include acoustic design and investigation, evaluation and calculation of noise, acoustic survey, building an architectural acoustics and air pressure testing. Whether you are a company or a private individual, we are here to advise and guide you. If you would like a friendly and accurate sound insulation testing quote, please send an email to info@af-acoustics.com or give us a call.

020 3372 4430 Contact us

Please send the following information to us

Give us the following information when contacting us

Place where the building is being built

Where in Charlbury the property is situated

Number of dwellings

Tell us how many dwellings you have in the property.

How many storeys are there?

For the right calculation of your quotation, tell us how many levels are in your building.

Dwellings arrangements per level

To help us get you an accurate quotation and evaluate the scope of the test to be taken, tell us how many dwellings there are per floor.

Kind of structure

Knowing the kind of building is essential because it helps identify the type of test that will be conducted.

New construction or refurbished building

The testing requirements for new dwellings and converted properties are not the same. Tell us the type of building you have so that we give you the right quote.

Sound testing regulations

We provide sound testing and sound insulation testing on all types of buildings, for compliance with Part E Building Regulations in England and Wales and Section 5 of the Scottish Building Standards. Testing can also gain credits for Code for Sustainable Homes and EcoHomes environmental assessment schemes.

Sound resistance and performance: Document E of Building Regulations (England and Wales)

We can send our authorised engineers to your development whenever the timing is ideal to undertake sound insulation testing that conforms to Building Regulations Document E consistence, as accepted by Building Control.

Scotland Standard division for properties

According to Section 5.1 of the Scottish Building Standards, “Every building must be designed and constructed in such a way that each wall and floor separating one dwelling from another, or one dwelling from another part of the building, or one dwelling from a building other than a dwelling, will limit the transmission of noise to the dwelling to a level that will not threaten the health of the occupants or inconvenience them in the course of normal domestic activities.” Tests should be performed after construction, using the procedures given in annex 5.C. of the Scottish Standards. Standard 5.1 does not apply to: fully detached houses or roofs or walkways with access solely for maintenance, or solely for the use of the residents of the dwelling below.

How to get a pass certificate for your sound test

Make sure you pass your sound test by having efficient sound insulation included in the building design. It saves time and money and helps you avoid repair work and re-test expenses. Are you uncertain that the separating floor and walls you will build will adhere to Document E 2003 conditions? You can book our design services. Whether you want some initial tests on your project, or comprehensive reports at the end, we can help you at the level that you need. The following will give you a better chance of passing the sound test: All windows and door have been fixed and are functioning Skirting boards are fixed are sealed Light fittings and switches and plug sockets are fitted and working. Our accomplished acoustic consultants work with developers, planners, contractors, and architects of all sizes from the early stages of the building plan to help limit any potential sound insulation performance problems to the completion of the construction, guaranteeing that all properties meet the criteria of Building Regulations Document E 2003.

Certificates for test evaluation and report

To obtain a thorough evaluation of your building, we issue a report certificate within 24 working hours where possible. Our highly capable sound test engineers will give you a verbal result of the test, once the test is taken and proffer solutions to possible problems or future areas of concern. 6. Even before you get the certificate, you get the verbal results of the test. First, our completely skilled and competent sound insulation test engineers give you a verbal result at the site. They also offer advice on potential problems. Then the test report certificate is sent to you within 24 working hours, when feasible.

The way the results look

A sound insulation certificate will be issued whether the Sound Testing results and report indicate compliance with Part E of the Building Regulations or not. If a partition wall or floor does not comply with Part E standards, repair work and another sound test will be needed. We can give robust advice on that to ensure you pass.


Sound Insulation FAQ’s

The minimum requirements depend on a variety of factors such as if the development is a new build or refurbished, whether the development is intended to be a permanent dwelling, or classified as “rooms of residential purposes” (e.g. hotels, student accommodation, etc).

New builds must achieve impact sound test results of no more than 62dB L’nTw and airborne sound insulation of no less than 45dB DnTw+Ctr. Converted properties must achieve impact results of 64dB L’nTw or lower and airborne sound insulation of no less than 43dB DnTw+Ctr.

Flanking sound (or flanking noise) is sound that transmits between spaces indirectly, going over or around, rather than directly through the main separating element. This can allow sound to transmit between spaces even though the main separating element itself provides good acoustic insulation. Engaging our services at an early stage allows us to check designs and add necessary measures to prevent this occurring after construction. In the worst cases, flanking can exceed the direct transmission and lead to a failed test, despite highly specified partitions.

In the case of impact sound, the building construction is caused to vibrate as a result of a physical impact, such as footsteps on floors or stairs. The resulting vibration is radiated into other rooms in the building.

We can provide preliminary results on the day of test. We strive to deliver next day reporting in all scenarios regardless the complexity or size of the project. The delivered report will be comprehensive and detailed, to ensure all relevant issues are covered. The best recommendations can also be sent in a separate report or email.

We can normally conduct up to a maximum of three sets of tests per day. One set is two airborne floor tests, two airborne wall tests and two impact floor sound tests.

When it comes to the acoustic tests, a full set of tests should take approximately 90 minutes.

The requirements of sound insulation testing are fully detailed in the Building Regulations Approved Document, available here [link], under Part E (2003).

This requires all residential buildings to be tested when they involve walls and/or floors. These are known as party elements.

Assuming no tests are failed, building control bodies should stipulate at least one set of tests for every ten dwelling-houses, flats or rooms for residential purposes in a group or sub-group.

New builds must achieve impact sound test results of no more than 62dB L’nTw and airborne sound insulation of no less than 45dB DnTw+Ctr. Converted properties must achieve impact results of 64dB L’nTw or lower and airborne sound insulation of no less than 43dB DnTw+Ctr.

We recommend that if possible, we are contacted before a build to provide a design review and advice on how to meet quality standards.

Should the test fail, we can offer advice on how to improve the sound insulation. We have consulted on hundreds of building projects in the past, and have ensured all of them have met the building regulations. If a sound insulation test fails, we can give remindial advice to ensure the tests passes later.

We understand that most clients would prefer testing to take place as soon as possible. Once you get in touch we will schedule the test at the earliest available opportunity.

You can call us today to set up an appointment for sound insulation testing. Our scheduling is flexible so that you can get the service you need at your convenience.

Ideally, a test should be carried out as early as possible as problems are more difficult to fix the further along you are. Where possible, it’s recommended that testing is carried out before kitchens or bathrooms are installed. The minimum that we require to be able to carry out a test is:

  • All doors, windows and seals should be fully fitted and closable
  • All electrical fittings should be fitted and working
  • 240V mains power must be available on-site in all rooms
  • Gaps in walls and floors should be fully sealed
  • All walls and ceilings should be plastered
  • There should be no holes remaining in floors or ceilings
  • Testers will require access to all rooms on all levels

Pre-completion sound testing is a building regulation requirement for all purpose built & “formed by material change of use” (i.e. refurbished) properties since 2003. Sound testing is undertaken in a percentage of properties in each development to ensure that the separating walls & floors between habitable rooms of neighbouring properties meet the minimum requirements as defined by Approved Document E, commonly referred to as ADE.

From 2003, Approved Document E states that all new UK builds must undergo pre-completion sound insulation testing. New builds must achieve impact sound test results of no more than 62dB L’nTw and airborne sound loss of no less than 45dB DnTw+Ctr. Converted properties must achieve impact results of 64dB L’nTw or lower and airborne sound loss of no less than 43dB DnTw+Ctr. Approved Document E sets out details pertaining to the resistance to the passage of sound.

This Approved Document, as part of UK Building Regulations helps to ensure that newly built or converted houses and residencies, flats and residential spaces and other relevant buildings are constructed to minimum standards that provide ‘reasonable resistance to sound from other parts of the same building and from adjacent buildings.’ All of our tests are fully compliant with Approved Document E and our expert team have been carrying out compliant tests for many years, for thousands of satisfied customers throughout the UK.

We understand the sectors our clients work in. Our advice is not only technically robust but also practical and helpful to our client’s particular situation. At AF Acoustics, we always look at the bigger picture and work towards the ultimate development goal.

In order to provide you best solutions, we will listen to your needs, present you with robust solutions and deliver acoustic consultancy through our considerable experience. Our ever-expanding knowledge-base allows us to provide cost-effective and streamlined solutions.

Our consultants are very experienced and have a proven track record on both small scale projects and major projects. As we are a lean and small company, we have lower overheads and therefore offer exceptional value for money.

Airborne sound (or airborne noise) is sound that is transmitted through the air. Airborne Sound Insulation is the insulation against noise originating in air, e.g. voices, music, motor traffic, wind. The greater the airborne sound insulation between two rooms, the lower the resulting sound level in the receiving room.

This is unlike Impact Sound Insulation that protects against noise originating directly on a structure by blows or vibration e.g. footsteps above, furniture being moved, drilling and hammering the structure.

Call us today for a quote on 020 3372 4430
Or you can email us at info@af-acoustics.com
Image module

Adrian Finn

AF Acoustics lead Acoustic Engineer, Adrian is your first port of call for all sound insulation testing questions enquiries and surveys.

Working Hours

  • Monday 08:00 - 18:00
  • Tuesday 08:00 - 18:00
  • Wednesday 08:00 - 18:00
  • Thursday 08:00 - 18:00
  • Friday 08:00 - 18:00
  • Saturday Closed
  • Sunday Closed